Welcome to our site! EDAboard.com is an international Electronics Discussion Forum focused on EDA software, circuits, schematics, books, theory, papers, asic, pld, 8051, DSP, Network, RF, Analog Design, PCB, Service Manuals... and a whole lot more! To participate you need to register. Registration is free. Click here to register now.
- Hardware and PCB Design
- Service Manuals, Requests, Repair Tips
You should upgrade or use an alternative browser.
[SOLVED] APC-Back UPS-RS 500 continuously clicking
- Thread starter Nathaniyelu
- Start date
- Status
- Not open for further replies.
- #1
relays are continuously clicking ..later i opened and found Two Electrolytic Caps bulged(each 4.7MF,450V) and one Cap(blackened--22MF,50V) i replaced all with new ones and connected to supply(220V 50Hz),now the UPS continuously beeping whenever switch ON,few days back i connected LCD monitor to UPS without mains..i.e on Battery ,LCD monitor was not ON but relays r continuously clicking...earlier Battery Charge without load..12.48V..now 9.3V. without battery there is 3V across battery charging terminals ..what could be the problem...,
Thanks in advance...
Attachments
- #2
At a glance i observe that ups is built in smps charger.
This page may be helpful, **broken link removed**
- #3
thank u for ur kind reply, i already checked above link which u suggested but no use...
- #4
- Joined
- Jan 28, 2013
- Messages
- 61
- Helped
- 7
- Reputation
- 14
- Reaction score
- 7
- Trophy points
- 1,288
- Activity points
- 1,601
- #5
What is the minimum voltage level of an UPS battery to ON..??
What will be the Full charge ..??
Thanks in advance.
- #6
- Joined
- Jan 28, 2013
- Messages
- 61
- Helped
- 7
- Reputation
- 14
- Reaction score
- 7
- Trophy points
- 1,288
- Activity points
- 1,601
UPS will power on ( Cold Start ) if the battery voltage is 11Vdc up...,
If the relay keeps on clicking most likely the problem is Caps, transistor (PNP & NPN) also IC (im not sure if that model came with LE50 or LP5050 IC its a 3 pins component),
- #7
- #8
A gel cell cannot tolerate too great a charge. Bubbles of gas develop on the lead plates. As I heard it, these bubbles do not disappear. They remain on the plates. This reduces the battery's power output, and shortens its useful life.
It is too soon for you to install a new battery. Right now you ought to check how much current is going into the present battery. It sounds as though it is ruined. Or in any case after 5 years we would expect it is used up.
Do you have an old 12V automobile battery? That would be more suitable for testing your UPS.
- #9
i dont know which type it is..the battery is made in China..CSB--UPS 240 model..
specifications
Standby use:13.5~13.8V
Cycle use: 14.4~15.0V
Initial current: 2A Max..
i don't have 12V automobile battery..
- #10
And by the way, you had asked about the thresh-hold voltage required for an inverter to work... Well it is about 10.5V ( as far as I can recapitulate from a few manuals)
- - - Updated - - -
Relays my be clicking because....
Under no load, the battery voltage may be rising just above the thresh-hold, but as soon as the battery is connected, even a small amount of current ( perhaps even the magnetization current required by the transformer) may be pulling down the voltage level below the thresh-hold. Thus activating the relay, and as soon the battery is disconnected the terminal voltage will rise again.... and the cycle continues.... This happens if the battery is no more in usable state. Although the no-load terminal voltage may be ok, the internal resistance may have risen beyond acceptable limits.
- #11
- Joined
- Jan 28, 2013
- Messages
- 61
- Helped
- 7
- Reputation
- 14
- Reaction score
- 7
- Trophy points
- 1,288
- Activity points
- 1,601
Hi Poweraces..,yesterday(6june2014)..i had found that the UPS Battery not recharging..and noticed it became bulged!!!(may be at the edge of Explode!!!) some chirping sound also coming.at this time i switched on UPS on mains there was continuous Beeping!!!.now i disconnected from UPS..and checked its voltage 9.2V..not raising anymore..seems need a New Battery.. you are not suspecting UPS Battery already its 5 years Old..!!??
the 9.2V is from battery or from UPS charging terminal? if the 9.2Vdc is battery you need to replace the battery. UPS battery usually use AGM type of battery. if the 9.2Vdc from the UPS terminal now your have a problem your charging ckt you need to fix that.
- #12
- #13
- #14
- Status
- Not open for further replies.
Similar threads
- APC Back-UPS 650MI PCB Fault
- Started by andrewclark
- Replies: 12
- APC RT-3000
- Started by Nenad5
- Replies: 3
- APC CS 650 BK650EI problem, need help
- Started by unchiu
- Replies: 0
- Hardware and PCB Design
- Service Manuals, Requests, Repair Tips
- This site uses cookies to help personalise content, tailor your experience and to keep you logged in if you register.
By continuing to use this site, you are consenting to our use of cookies.
armstronglart1967.blogspot.com
Source: https://www.edaboard.com/threads/apc-back-ups-rs-500-continuously-clicking.315594/
0 Response to "Apc Rs1500 Switches From Online to on Battery Continually"
Post a Comment